SGB were founded in 1962 and were the inventor of the vacuum leak detection systems for single skinned tanks. Today they have more than 40 different types of leak detectors with more than 100 variations.

SGB Leak Detection Systems aim to provide a leak free and monitored environment. SGB measurement units use either pressure or vacuum monitoring technology for accurately testing double walled tanks and pipes whilst in service.

SGB Leak Detection Systems give a visual and audible alarm indication before any stored product can enter the environment and cause environmental pollution.

SGB systems are approved to prEN13160 as Class 1 Leak Detection Systems and are approved as safe technology for the monitoring of:

 

Double walled tanks and double walled pipes on petrol stations Aboveground or underground tanks that bulk store any type of water polluting liquid.
For example in tank farms, chemical plants or refineries

Heating or Fuel Oil storage tanks fitted with double bottoms or fully double skinned

Listed below are some of the SGB products which Orange County Supply.

For more information on SGB visit the website SGB Website

DL-330 Pressure Leak Detection System

DL - 330

  • Pressure leak detector with integrated pump within plastic housing for the monitoring of serveral underground tanks or one aboveground tank.
  • Type with alarmpressure in mbar:
    DL 330
  • Tanks:
    double walled cylindrical laying tanks with a non permeable inner wall and a test pressure of the interstitial space of 500 mbar, e.g. DIN 6608, 6616 or EN 12285 or other approved tanks
  • Liquids:
    water polluting liquids
    e.g.: gasoline, petrol, methanol, kerosene, jet, diesel
  • Germany: Z - 65.23 - 409,
    CE marked, in accordance to EN 13160, Class I
  • Accessories as manifolds, tank adapters, are available for PVC hoses or PA (Polyamide) hoses and for copper tubing

For more detailed information download the data sheet DL-330 Pressure Leak Detector


DLR-G Pressure Leak Detection System - click to go to BRUGG Pipe Sytems Page

DLR - G

  • Pressure leak detector with automatic refill function from a permanent connected inert gas (nitrogen) bottle, operation mode S for underground and aboveground installed pipes.
  • With selectable operation mode M without automatic refill function. In operation mode M only to be used for applications in which temperature changes in the connected pipework are low. E.g. underground pipes.
  • Types with alarm pressures in bar:
    DLR-G 1; DLR-G 2; DLR-G 3; … DLR-G 17; DLR-G 18
  • double walled pipes or vessels out of metal or plastic for
    water polluting liquids:
    e.g. petrol, jet, methanol, diesel, chemicals, lye, acids
  • Germany: Z-65.26 - 349

For more detailed information download the data sheet DLR-G Nitrogen Pressure Leak Detector


DLR-P Pressure Leak Detection - click to go to BRUGG Pipe Sytems Page

DLR - P

  • Pressure leak detector with integrated pump.
  • Types with alarm pressures in bar:
    DLR-P 1.1; DLR-P 2.3; DLR-P 3.0
  • double walled pipes or vessels.
  • water polluting liquids:
    on pipes with a non permeable inner wall also liquids with a flash point below 55° Celsius,
    e.g. heating oil, diesel, engine oil, petrol, jet, methanol, lye, acid
  • Germany: Z-65.26 -349
  • advantages:
    low maintenance in comparison to systems working with nitrogen.

For more detailed information download the data sheet DLR-P Pressure Leak Detector

 

VL-34 Vacuum Leak Detector

VL 34

  • Vacuum leak detection system to monitor single walled tanks equipped with a lining. A suction line to the deepest point of the interstitial space is required.
  • Type with alarm pressure in mbar:
    VL 34
  • Alarm underpressure: > 34 mbar; operating pressure: < 90 mbar
  • Tanks:
    - single walled tanks with a lining, e.g. DIN 6608, 6616, 6625
    - double walled tanks with a suction line to the bottom of the interstice, e.g. DIN 6618/2
  • liquids with a flash-point above > 55°C; e.g. heating oil, diesel, engine oil
  • Germany: Z - 65.22 - 389

For more detailed information download the data sheet VL-34 Vacuum Leak Detection


VL-330 Vacuum Leak Detector

VL 330

  • Vacuum leak detection system to monitor double walled steel or plastic tanks.
  • Type with alarm pressure in mbar:
    VL 330
  • Alarm under pressure: > 330 mbar; operating pressure: < 450 mbar
  • Tanks:
    - double walled cylindrical tanks e.g. DIN 6608; 6616, 6617, 6623, 6624
    - single walled tanks with an approved lining
    - upright standing tanks with suction line e.g. DIN 6618/2;
    - other approved tanks
  • liquids with a flash-point above > 55°C; e.g. heating oil, diesel, engine oil
  • Germany: Z - 65.22 - 389

For more detailed information download the data sheet VL-330 Vacuum Leak Detection

 

VLX A-Ex Vacuum Leak Detector

VLX../A-Ex

  • Divided Vacuum Leak detection system consisting of an explosion protected working unit VLX../A-EX and non explosion protected indicating units VLX ME for one working unit or VLX ZME for up to 10 working units.
  • Types with alarm under pressures in mbar:
    VLX 34/A-Ex; VLX 330/A-Ex
  • Tanks:
    - single laying (under- /aboveground), cylindrical tanks with lining or jacketing
    - d
    ouble walled laying cylindrical (under- / aboveground) tanks.
    - d
    ouble walled (or single walled with lining or jacketing) upright standing tanks or sumps with dished bottom (under-/aboveground)
  • Rectangular or cylindrical tanks or sumps with flat bottom (complete double walled or with lining or jacketing)
    water polluting liquids;
    hazardous vapors of the liquids must be classified in group II A or II B 3 and in temperature classes T 1 up to T 3
    e.g.: gasoline/ petrol, jet fuel, diesel, chemicals, lye, acid
    Designs in brass (MS) or stainless steel (V4A)
  • Germany: Z - 65.22 -340

For more detailed information download the data sheet VLX A-Ex Vacuum Leak Detection

 

VLX A-Ex Vacuum Leak Detector
VLX-EX Vacuum Leak Detector

VLX../Ex

  • Explosion Protected Vacuum Leak Detection to be installed in zone 1 or 2.
  • Types with alarm under pressures in mbar:
    VLX 34/Ex and VLX 330/Ex
  • Tanks:
  • single laying (under- /aboveground), cylindrical tanks with lining or jacketing
  • Double walled laying cylindrical (under- / aboveground) tanks.
  • Double walled (or single walled with lining or jacketing) upright standing tanks or sumps with dished bottom (under-/aboveground)
  • Rectangular or cylindrical tanks or sumps with flat bottom (complete double walled or with lining or jacketing)
  • water polluting liquids;
    hazardous vapors of the liquids must be classified in group II A or II B 3 and in temperature classes T 1 up to T 3
    e.g.: gasoline/ petrol, jet fuel, diesel, chemicals, lye, acid
  • Designs in brass (MS) or stainless steel (V4A)
  • Germany: Z - 65.22 - 340

For more detailed information download the data sheet VLX-EX Vacuum Leak Detection

 

VLR-410/E

  • Three way cocks in suction- and measuring-line allow the quickest and easiest function check of the system
  • Simple and quick mounting through an improved design
  • Electronic management with integrated tightness analysis of the entire system
  • Connection of an additional sensor for sump monitoring with a separate alarm indication is possible

Alarm underpressure: 410 mbar

Tanks: Double walled pipes and hoses

Liquids: Liquids with a flash-point > 55°C, e.g: heating oil, diesel, engine oil, lye and acid (if chemical resistance is given)

Approvals: Z 65.25-390

For more detailed information download the data sheetVLX-EX Vacuum Leak Detection

 

 

For more information on SGB visit the website SGB Website

© Orange County Limited 2007 | Company No. 2967852
t: +44(0)1388 813433 | f: +44(0)1388 813307